EarthSpotterEarthSpotter

Crockett Cogeneration

550 Loring Avenue, Crockett, CA 94525

Crockett Cogeneration operates the site. Its industry is listed as power plant. It reported values over its permit's limit 5 times in the last three years.

550 Loring Avenue, Crockett

Industrial wastewater

Values this facility reported were over the permit's limit 5 times in the last three years.

Most recently, %Surv static renewal 96Hr oncorhynchus mykiss at EFF-001 was 45 % survival as a minimum, 36% under the minimum of 70 % survival. The Water Board took 8 enforcement actions, 4 of which required a penalty.

Clean WaterIndustrial wastewater

Reported value over the permit's limit

Clean Water Act. Source: California State Water Resources Control Board and U.S. Environmental Protection Agency, data as of November 25, 2026.

Facility type
Industrial wastewater discharger
Discharger
Crockett Cogeneration
Regional Water Board
Region 2
Size
Minor facilityAs the EPA classes it.
Design flow
0.5 million gallons a day
Discharges to
Carquinez Strait

What the public records hold

Monitoring results
57 parameters at 2 monitoring points, latest Sep 30, 2026
Permit limits
10 parameters with limits
Reported values over the permit's limit, last three years
5
Violations the Water Board recorded
Not available
Enforcement actions
8Has been required to pay penalties.

Permits

PermitTypeStatusEffectiveExpires
CA0029904Order R2-2021-0025Individual permitActiveFeb 1, 2022Jan 31, 2027
CA0038849Order R2-2017-0041Co-permitteeActive, past its expiration dateThe permit stays in force until the Water Board renews it.Jan 1, 2013Dec 31, 2017

What the facility reported

Results the facility reported to the state for the last three years, one row per pollutant as the permit lists them. A pollutant over its limit opens to each value over: which limit, where, and when. Each month shows the monthly average the facility reported, or the highest result that month when it filed no average.

What it discharges
ParameterLatest resultPermit limitsHistory
Copper, totalEFF-0011.2 ug/LDec 31, 2025Monthly average 40 ug/L. Daily maximum 120 ug/L.Monthly average 40 ug/L: once. Daily maximum 120 ug/L: once.
%Surv Static Renewal 96Hr Oncorhynchus mykissEFF-00145 % survivalDec 31, 2025Minimum 70 % survival. Median minimum 90 % survival.Minimum 70 % survival: once. Median minimum 90 % survival: once.
CyanideEFF-0014.6 ug/LDec 31, 2025Monthly average 15 ug/L. Daily maximum 46 ug/L.Daily maximum 46 ug/L: once.
pHEFF-0016.5 SUSep 30, 2026Minimum 6 SU. Maximum 9 SU.None over the limit
Zinc, totalEFF-0019.5 ug/LDec 31, 2025Monthly average 230 ug/L. Daily maximum 600 ug/L.None over the limit
Total suspended solidsAt EFF-001, in mg/L and lb/dayMonthly average 30 mg/L. Daily maximum 45 mg/L.Monthly average 44 lb/d. Daily maximum 67 lb/d.None over the limit
Acute toxicity% survival (Pimephales promelas), EFF-00195 % survivalDec 31, 2025Minimum 70 % survival. Median minimum 90 % survival.None over the limit
Oil and greaseAt EFF-001, in lb/d and mg/LMonthly average 15 lb/d. Daily maximum 30 lb/d.Monthly average 10 mg/L. Daily maximum 20 mg/L.None over the limit
Mercury, total recoverableEFF-SUM0.0011 kg/yrSep 30, 2025Annual average 0.0047 kg/yr.None over the limit
Mercury, totalAt EFF-001, in ug/L and ng/LMonthly average 0.079 ug/L. Daily maximum 0.12 ug/L.None over the limit
FlowEFF-001146,831 GPDJun 30, 2026No limit
Biochemical oxygen demand (BOD)EFF-001Not detectedDec 31, 2025No limit
Total residual chlorineEFF-0010.04 mg/LJun 3, 2025No limit
TemperatureEFF-0015.5 Degrees FJun 1, 2026No limit
1,2-DichlorobenzeneEFF-001Not detectedDec 31, 2025No limit
1,3-DichlorobenzeneEFF-001Not detectedDec 31, 2025No limit
1,4-DichlorobenzeneEFF-001Not detectedDec 31, 2025No limit
Arsenic, totalEFF-0010.57 ug/LDec 31, 2025No limit
Cadmium, totalEFF-001Not detectedDec 31, 2025No limit
Chromium (Total)EFF-0010.53 ug/LDec 31, 2025No limit
Lead, totalEFF-001Not detectedDec 31, 2025No limit
Nickel, totalEFF-0011.2 ug/LDec 31, 2025No limit
Selenium, totalEFF-001Not detectedDec 31, 2025No limit
Silver, totalEFF-001Not detectedDec 31, 2025No limit
Thallium, totalEFF-001Not detectedDec 31, 2025No limit
1,1-DichloroethaneEFF-001Not detectedDec 31, 2025No limit
1,1-DichloroethyleneEFF-001Not detectedDec 31, 2025No limit
1,1,1-TrichloroethaneEFF-001Not detectedDec 31, 2025No limit
1,1,2-TrichloroethaneEFF-001Not detectedDec 31, 2025No limit
1,1,2,2-TetrachloroethaneEFF-001Not detectedDec 31, 2025No limit
1,2-DichloroethaneEFF-001Not detectedDec 31, 2025No limit
1,2-DichloropropaneEFF-001Not detectedDec 31, 2025No limit
1,2-DiphenylhydrazineEFF-001Not detectedDec 31, 2025No limit
1,2,3-TrichloropropaneEFF-001Not detectedDec 31, 2025No limit
1,2,3,4,6,7,8-Heptachlorodibenzo-p-dioxinEFF-001Not detectedDec 31, 2025No limit
1,2,3,4,6,7,8-HeptachlorodibenzofuranEFF-001Not detectedDec 31, 2025No limit
1,2,3,4,6,7,8,9-Octachlorodibenzo-p-dioxinEFF-001Not detectedDec 31, 2025No limit
1,2,3,4,6,7,8,9-OctachlorodibenzofuranEFF-001Not detectedDec 31, 2025No limit
1,2,3,4,7,8-Hexachlorodibenzo-p-dioxinEFF-001Not detectedDec 31, 2025No limit
1,2,3,4,7,8-HexachlorodibenzofuranEFF-001Not detectedDec 31, 2025No limit
1,2,3,4,7,8,9-HeptachlorodibenzofuranEFF-001Not detectedDec 31, 2025No limit
1,2,3,6,7,8-Hexachlorodibenzo-p-dioxinEFF-001Not detectedDec 31, 2025No limit
1,2,3,6,7,8-HexachlorodibenzofuranEFF-001Not detectedDec 31, 2025No limit
1,2,3,7,8-Pentachlorodibenzo-p-dioxinEFF-001Not detectedDec 31, 2025No limit
1,2,3,7,8-PentachlorodibenzofuranEFF-001Not detectedDec 31, 2025No limit
1,2,3,7,8,9-Hexachlorodibenzo-p-dioxinEFF-001Not detectedDec 31, 2025No limit
1,2,3,7,8,9-HexachlorodibenzofuranEFF-001Not detectedDec 31, 2025No limit
1,2,4-TrichlorobenzeneEFF-001Not detectedDec 31, 2025No limit
2-Chloroethylvinyl EtherEFF-001Not detectedDec 31, 2025No limit
2-ChloronaphthaleneEFF-001Not detectedDec 31, 2025No limit
2-ChlorophenolEFF-001Not detectedDec 31, 2025No limit
2-MethylnaphthaleneEFF-001Not detectedDec 31, 2025No limit
2-MethylphenolEFF-001Not detectedDec 31, 2025No limit
2-NitroanilineEFF-001Not detectedDec 31, 2025No limit
2-NitrophenolEFF-001Not detectedDec 31, 2025No limit
2,3,4,6,7,8-HexachlorodibenzofuranEFF-001Not detectedDec 31, 2025No limit
2,3,4,7,8-PentachlorodibenzofuranEFF-001Not detectedDec 31, 2025No limit

Reported values over the permit's limit

Monthly reports the facility filed with the EPA, compared with the permit's limit for the same measure. A value counts only when it was detected and the limit was in force on that date.

Every value over the limit, by date (5)
Period endingParameterMeasureReportedLimitOver by
Dec 31, 2025%Surv Static Renewal 96Hr Oncorhynchus mykissEFF-001EPA lists this as a violation.Minimum45 % survival70 % survival36% under the minimum
Dec 31, 2025%Surv Static Renewal 96Hr Oncorhynchus mykissEFF-001EPA lists this as a violation.Median minimum45 % survival90 % survival50% under the minimum
Apr 30, 2025CyanideEFF-001EPA lists this as a violation.Daily maximum48 ug/L46 ug/L4% over
Nov 30, 2023Copper, totalEFF-001EPA lists this as a violation.Monthly average87 ug/L40 ug/L118% over
Nov 30, 2023Copper, totalEFF-001EPA lists this as a violation.Daily maximum260 ug/L120 ug/L117% over

Violations the Water Board recorded

Not available. The Water Board's violation records for this kind of facility are not published as data we can read.

Enforcement actions

Notices, orders, and penalties the Water Board issued.

DateActionDetailsPenalty
Apr 1, 2025Administrative Civil LiabilityOrder R2-2025-1006MMPThe Water Board marks this as a mandatory minimum penalty.Status: HistoricalPenalty required
Oct 25, 2022Administrative Civil LiabilityOrder R2-2022-1012MMPThe Water Board marks this as a mandatory minimum penalty.Status: HistoricalPenalty required
Dec 7, 2015Administrative Civil LiabilityOrder R2-2015-1026MMPThe Water Board marks this as a mandatory minimum penalty.Status: HistoricalPenalty required
May 20, 2015Oral CommunicationOn May 20, 2015 Crockett Cogeneration submitted response to the 1/23/2015 Notice of Violation and followed up by submitting an updated Stormwater Pollution Prevention Plan in July 2015. The Discharger's response is considered adequate.Status: Historical
Dec 31, 2012Oral CommunicationDiscussed with the Discharger; concurred with their proposed corrective measures.Status: Historical
Sep 6, 2011Oral CommunicationDiscussed accelerated sampling and reporting requirements, possible causes and corrective actions.Status: Historical
Nov 19, 2008Administrative Civil LiabilityOrder SWB-2008-2-0006Status: HistoricalPenalty required
Jul 24, 2008Letter to Regulated Entity

Sources: the State Water Board's permit, monitoring, and enforcement records (CIWQS) and the EPA's monthly reports and permit limits (ICIS-NPDES). The Water Board's record for this facility (CIWQS).

Location and details

The neighborhood

About 3,212 people live in the neighborhood around this site in Martinez. The state scores it above 39% of California neighborhoods for pollution burden and health vulnerability.

Least burdenedMost burdened

Source: CalEnviroScreen 5.0, census tract 6013357000. The score covers the whole neighborhood and does not measure this site's own effect.

Permits and IDs

Industry
Power Plant
Operator
Crockett Cogeneration
Covered by
Wastewater discharge permit
EPA registry ID
110001163062

The Water Board's record for this facility (CIWQS)
The EPA's record for this site

Report pollution at this site