San Juan Bautista City, a city agency, operates the site. Its industry is listed as wastewater treatment facility. It reported values over its permit's limit 21 times in the last three years.

1120 Third Street, San Juan Bautista

Municipal wastewater

Values this facility reported were over the permit's limit 21 times in the last three years.

Most recently, chloride at M-001 was 306 mg/L as a monthly average, 53% over the limit of 200 mg/L. The Water Board took 23 enforcement actions, 6 of which required a penalty.

Clean WaterMunicipal wastewater

Reported value over the permit's limit

Clean Water Act. Source: California State Water Resources Control Board and U.S. Environmental Protection Agency, data as of November 25, 2026.

Facility type
Sewage treatment plant
Discharger
San Juan Bautista City
Regional Water Board
Region 3
Size
Minor facilityAs the EPA classes it.
Design flow
0.27 million gallons a day
Discharges to
Chino Creek Reach 1

What the public records hold

Monitoring results
25 parameters at 3 monitoring points, latest Dec 31, 2025
Permit limits
15 parameters with limits
Reported values over the permit's limit, last three years
21
Violations the Water Board recorded
Not available
Enforcement actions
23Has been required to pay penalties.

Permit

PermitTypeStatusEffectiveExpires
CA0047902Order R3-2009-0019Individual permitActive, past its expiration dateThe permit stays in force until the Water Board renews it.May 9, 2009May 8, 2014

What the facility reported

Results the facility reported to the state for the last three years, one row per pollutant as the permit lists them. A pollutant over its limit opens to each value over: which limit, where, and when. Each month shows the monthly average the facility reported, or the highest result that month when it filed no average.

What it discharges
ParameterLatest resultPermit limitsHistory
ChlorideM-001307 mg/LJun 9, 2025Monthly average 200 mg/L.Monthly average 200 mg/L: 14 times.
Total suspended solidsM-00118 mg/LJun 9, 2025Monthly average 20 mg/L. Daily maximum 60 mg/L. Highest weekly average 45 mg/L.Monthly average 20 mg/L: 2 times. Daily maximum 60 mg/L: once.
Total coliformM-00128 MPN/100mLJun 9, 2025Instantaneous maximum 2,300 MPN/100mL. Median 23 MPN/100mL.Instantaneous maximum 2,300 MPN/100mL: once. Median 23 MPN/100mL: once.
Total suspended solids, percent removalM-00196 %Jun 30, 2025Monthly average minimum 85 %.Monthly average minimum 85 %: once.
Biochemical oxygen demand (BOD)M-00113 mg/LJun 9, 2025Monthly average 20 mg/L. Daily maximum 60 mg/L. Highest weekly average 45 mg/L.Daily maximum 60 mg/L: once.
BOD, percent removalM-00197 %Jun 30, 2025Monthly average minimum 85 %.None over the limit
Total residual chlorineM-0010 mg/LJun 30, 2025Instantaneous maximum 0.1 mg/L.None over the limit
pHM-0018 SUJun 9, 2025Minimum 6 SU. Maximum 9 SU.None over the limit
Settleable solidsM-001Not detectedJun 8, 2025Monthly average 0.1 mL/L. Daily maximum 0.3 mL/L.None over the limit
Total dissolved solidsM-0011,120 mg/LJun 9, 2025Monthly average 1,400 mg/L.None over the limit
Sodium, TotalM-001244 mg/LJun 9, 2025Monthly average 250 mg/L.None over the limit
SulfateM-001153 mg/LJun 30, 2025Monthly average 350 mg/L.None over the limit
Oil and greaseM-001Not detectedJun 3, 2025Monthly average 10 mg/L. Daily maximum 20 mg/L.None over the limit
Chronic toxicity3 tests at M-001Daily maximum 1 tox chronic.None over the limit
Un-ionized ammonia (as N)M-001Not detectedApr 25, 2025Daily maximum 0.025 mg/L.None over the limit
FlowM-0010 MGDJun 30, 2025No limit
TemperatureM-00121 Degrees CJun 9, 2025No limit
Dissolved oxygenM-0016.4 mg/LMay 27, 2025No limit
Nitrate (as N)M-0010.5 mg/LJun 3, 2025No limit
Ammonia (as N)M-0011.1 mg/LApr 25, 2025No limit
Color, Pt-Co (unfiltered)M-001100 Pt-Co Color UnitJun 3, 2025No limit
Hardness, Ca (as CaCO3)M-001434 mg/LJun 3, 2025No limit
Total phosphorus (as P)M-0013.4 mg/LJun 3, 2025No limit
Sulfate, Total (as S)M-001153 mg/LJun 3, 2025No limit
The water it discharges to
ParameterLatest resultPermit limitsHistory
Dissolved oxygenAt R-SW1 and R-SW2No limit
pHAt R-SW1 and R-SW2No limit
TemperatureAt R-SW1 and R-SW2No limit
TurbidityAt R-SW1 and R-SW2No limit

Reported values over the permit's limit

Monthly reports the facility filed with the EPA, compared with the permit's limit for the same measure. A value counts only when it was detected and the limit was in force on that date.

Every value over the limit, by date (21)
Period endingParameterMeasureReportedLimitOver by
Jun 30, 2025ChlorideM-001EPA lists this as a violation.Monthly average306 mg/L200 mg/L53% over
May 31, 2025ChlorideM-001EPA lists this as a violation.Monthly average289 mg/L200 mg/L45% over
Apr 30, 2025Biochemical oxygen demand (BOD)M-001EPA lists this as a violation.Daily maximum69 mg/L60 mg/L15% over
Apr 30, 2025ChlorideM-001EPA lists this as a violation.Monthly average263 mg/L200 mg/L31% over
Mar 31, 2025ChlorideM-001EPA lists this as a violation.Monthly average256 mg/L200 mg/L28% over
Feb 28, 2025ChlorideM-001EPA lists this as a violation.Monthly average265 mg/L200 mg/L33% over
Jan 31, 2025ChlorideM-001EPA lists this as a violation.Monthly average278 mg/L200 mg/L39% over
Nov 30, 2024ChlorideM-001EPA lists this as a violation.Monthly average285 mg/L200 mg/L42% over
Oct 31, 2024ChlorideM-001EPA lists this as a violation.Monthly average294 mg/L200 mg/L47% over
Oct 31, 2024Total coliformM-001EPA lists this as a violation.Instantaneous maximum2,420 MPN/100mL2,300 MPN/100mL5% over
Oct 31, 2024Total coliformM-001EPA lists this as a violation.Median242 MPN/100mL23 MPN/100mL951% over
Sep 30, 2024ChlorideM-001EPA lists this as a violation.Monthly average288 mg/L200 mg/L44% over
Aug 31, 2024ChlorideM-001EPA lists this as a violation.Monthly average280 mg/L200 mg/L40% over
Jul 31, 2024ChlorideM-001EPA lists this as a violation.Monthly average269 mg/L200 mg/L35% over
Jul 31, 2024Total suspended solidsM-001EPA lists this as a violation.Daily maximum64 mg/L60 mg/L7% over
Jun 30, 2024Total suspended solidsM-001EPA lists this as a violation.Monthly average26 mg/L20 mg/L30% over
May 31, 2024ChlorideM-001EPA lists this as a violation.Monthly average229 mg/L200 mg/L14% over
May 31, 2024Total suspended solids, percent removalM-001EPA lists this as a violation.Monthly average minimum79 %85 %7% under the minimum
May 31, 2024Total suspended solidsM-001EPA lists this as a violation.Monthly average22 mg/L20 mg/L10% over
Jan 31, 2024ChlorideM-001EPA lists this as a violation.Monthly average239 mg/L200 mg/L19% over
Dec 31, 2023ChlorideM-001EPA lists this as a violation.Monthly average268 mg/L200 mg/L34% over

Violations the Water Board recorded

Not available. The Water Board's violation records for this kind of facility are not published as data we can read.

Enforcement actions

Notices, orders, and penalties the Water Board issued.

DateActionDetailsPenalty
Oct 31, 2023Administrative Civil LiabilityOrder R3-2023-0076EPL offer to settle 12 effluent violations for the mandatory minimum penalty of $36,000.The Water Board marks this as a mandatory minimum penalty.Status: HistoricalPenalty required
Feb 13, 2023Administrative Civil LiabilityOrder R3-2023-0004Offer to settle 11 violations of chloride, total coliform, and sodium effluent limits for the mandatory minimum penalty of $33,000.The Water Board marks this as a mandatory minimum penalty.Status: HistoricalPenalty required
Oct 18, 2022Administrative Civil LiabilityOrder R3-2022-0031ACL order addresses 327 effluent limit violations from 3/31/2007 through 3/31/2022 for $981,000 with $111,000 dismissed for laches, $174,000 paid to CAA, and $696,000 suspended pending completion of a Compliance Project.Status: ActivePenalty required
Aug 26, 2020CWA 309A AO For Compliance
Nov 28, 2012Administrative Civil LiabilityOrder R3-2012-0040Expedited Payment Program Offer R3-2010-0045 transmitted to discharger to resolve MMP for 13 serious violations spanning 5/31/2009 - 6/30/2010 for a total liability of $39,000. Discharger responded with signed waiver and request for SEP. During SEP development, parties extended violation date range to include 38 violations up to 6/30/2012, and liability of $114,000, and documented settlement in Stipulated ACL R3-2012-0040.The Water Board marks this as a mandatory minimum penalty.Status: HistoricalPenalty required
Oct 21, 2009Administrative Civil LiabilityOrder R3-2009-0076EPL for MMP. Note that the NOV attached to the EPL incorrectly listed Violation # 829824, although the other details of the entry were correct. The correct Violation # is 844768.The Water Board marks this as a mandatory minimum penalty.Status: HistoricalPenalty required
Jul 1, 2008Letter to Regulated Entity
Jul 2, 2007Notice of ViolationOn Sept. 6, 2006 and Dec. 11, 2006, the City's wastewater discharge exceeded the permitted effluent chloride monthly average of 200 mg/L by 38% (276 mg/L reported value). On March 13, 2007, the City's wastewater discharge exceeded the permitted effluent chloride monthly average of 200 mg/L by 43% (286 mg/L reported value).Status: Historical
Sep 7, 2006Notice of ViolationNOV issued for discharging waste without regulation by permit; failure to properly notify Water Board of said discharge.Status: Historical
Dec 5, 2003Administrative Civil LiabilityOrder R3-2003-0141Mandatory Minimum Penalty for serious violations.The Water Board marks this as a mandatory minimum penalty.Status: HistoricalPenalty required
Jan 8, 2003Notice of ViolationOrder UNKNOWNTwo sewage spills violated Order.Status: Historical
Aug 29, 2001Notice of ViolationOrder UNKNOWNStatus: Historical
Jul 13, 2001Cease and Desist OrderOrder 01-106Discharger exceeded effluent chloride concentrations on monthly basis since December 2000Status: Historical
May 16, 2001Notice of ViolationOrder UNKNOWNViolations of monthly chloride effluent limits..exceedances each month since DecemberStatus: Historical
Feb 8, 2001Investigative order (Water Code 13267)Order UNKNOWNStaff sent letter requesting spill prevention program for review.Status: Historical
Mar 16, 1995Cease and Desist OrderOrder 95-094RESCINDS ORDER 93-090.Status: Historical
Nov 12, 1993Cease and Desist OrderOrder 93-090TIME SCHEDULE REQUIREMENTS ADOPTED FOR CONSTRUCTING ADDITIONAL TREATMENT PROCESSES.Status: Historical
Nov 8, 1991Cease and Desist OrderOrder 91-124REVISION OF AVERAGE DAILY FLOW LIMITS.Status: Historical
Mar 12, 1988State CWA Non Penalty AO
Mar 11, 1988Cease and Desist OrderOrder 88-029NONEStatus: Historical
Nov 15, 1987State CWA Non Penalty AO
Sep 6, 1985Cease and Desist OrderOrder 85-138ILLEGAL DISCHARGES TO DRAINAGE CHANNEL/S BENITO RIVERStatus: Historical
Sep 6, 1985State CWA Non Penalty AO

Sewer spills from San Juan Bautista CS

The same agency runs the sewer system that feeds this plant. Spills are reported under the State Water Board's sewer system order, a state program separate from this permit. Category 1 spills reached surface water.

None

Sources: the State Water Board's permit, monitoring, and enforcement records (CIWQS) and the EPA's monthly reports and permit limits (ICIS-NPDES). The Water Board's record for this facility (CIWQS).

Location and details

The neighborhood

About 6,748 people live in the neighborhood around this site in San Juan Bautista. The state scores it above 46% of California neighborhoods for pollution burden and health vulnerability.

Least burdenedMost burdened

Source: CalEnviroScreen 5.0, census tract 6069000200. The score covers the whole neighborhood and does not measure this site's own effect.

Permits and IDs

Industry
Wastewater Treatment Facility
Operator
San Juan Bautista City
Covered by
Wastewater discharge permit
EPA registry ID
110009126999

The Water Board's record for this facility (CIWQS)