Graton CSD operates the site. Its industry is listed as wastewater treatment facility. It reported values over its permit's limit 3 times in the last three years.
250 Ross, Sebastopol
Municipal wastewater
Values this facility reported were over the permit's limit 3 times in the last three years.
Most recently, total coliform at EFF-001 was 4.5 MPN/100mL as a 7-day median, 105% over the limit of 2.2 MPN/100mL. The Water Board took 16 enforcement actions, 4 of which required a penalty.
Clean WaterMunicipal wastewater
Reported value over the permit's limit
Clean Water Act. Source: California State Water Resources Control Board and U.S. Environmental Protection Agency, data as of November 25, 2026.
Facility type
Sewage treatment plant
Discharger
Graton CSD
Regional Water Board
Region 1
Size
Minor facilityAs the EPA classes it.
Design flow
0.14 million gallons a day
Discharges to
Atascadero Creek (Region 1)
What the public records hold
Monitoring results
21 parameters at 4 monitoring points, latest Sep 30, 2026
Permit limits
11 parameters with limits
Reported values over the permit's limit, last three years
3
Violations the Water Board recorded
Not available
Enforcement actions
16Has been required to pay penalties.
Permit
Permit
Type
Status
Effective
Expires
CA0023639Order R1-2018-0001
Individual permit
Active, past its expiration dateThe permit stays in force until the Water Board renews it.
Aug 1, 2018
Jul 31, 2023
What the facility reported
Results the facility reported to the state for the last three years, one row per pollutant as the permit lists them. A pollutant over its limit opens to each value over: which limit, where, and when. Each month shows the monthly average the facility reported, or the highest result that month when it filed no average.
What it discharges
Parameter
Latest result
Permit limits
History
Total coliformAt EFF-001 and EFF-002
7-day median 2.2 MPN/100mL. 30-day maximum 23 MPN/100mL. Maximum single sample 240 MPN/100mL.7-day median 2.2 MPN/100mL: 3 times.
Total residual chlorineAt EFF-001 and EFF-002
Monthly average 0.01 mg/L. Daily maximum 0.02 mg/L.None over the limit
pHAt EFF-001 and EFF-002
Minimum 6.5 SU. Maximum 8.5 SU.None over the limit
Biochemical oxygen demand (BOD)EFF-001
Not detectedSep 28, 2026
Monthly average 10 mg/L. Weekly average 15 mg/L.None over the limit
Total suspended solidsEFF-001
2.4 mg/LSep 28, 2026
Monthly average 10 mg/L. Weekly average 15 mg/L.None over the limit
BOD, percent removalEFF-001
99 %Sep 30, 2026
Monthly average minimum 85 %.None over the limit
Total suspended solids, percent removalEFF-001
99 %Sep 30, 2026
Monthly average minimum 85 %.None over the limit
Ammonia (as N)EFF-002
1.4 mg/LFeb 3, 2026
Monthly average 5.6 mg/L. Daily maximum 13 mg/L.None over the limit
Minimum 70 % survival. Median minimum 90 % survival.None over the limit
Acute toxicity2 tests at EFF-002
Minimum 70 % survival. Median minimum 90 % survival.None over the limit
TCDD equivalentsEFF-002
Not detectedJan 6, 2026
Monthly average 0.000014 ng/L. Daily maximum 0.000028 ng/L.None over the limit
TemperatureAt EFF-001 and EFF-002
No limit
Dissolved oxygenEFF-002
8 mg/LFeb 28, 2026
No limit
Un-ionized ammonia (as N)EFF-002
0.016 mg/LFeb 3, 2026
No limit
Nitrate (as N)EFF-002
2.5 mg/LFeb 3, 2026
No limit
Total phosphorus (as P)EFF-002
1 mg/LFeb 3, 2026
No limit
Hardness (as CaCO3)EFF-002
140 mg/LJan 6, 2026
No limit
Chronic toxicityChronic toxicity, EFF-002
Not detectedFeb 10, 2025
No limit
The water it discharges to
Parameter
Latest result
Permit limits
History
FlowRSW-001
34 MGDFeb 28, 2026
No limit
pHAt RSW-001 and RSW-002
No limit
TemperatureAt RSW-001 and RSW-002
No limit
Ammonia (as N)At RSW-001 and RSW-002
No limit
Un-ionized ammonia (as N)At RSW-001 and RSW-002
No limit
Dissolved oxygenAt RSW-001 and RSW-002
No limit
Hardness, Ca (as CaCO3)At RSW-001 and RSW-002
No limit
Nitrate (as N)At RSW-001 and RSW-002
No limit
Total phosphorus (as P)At RSW-001 and RSW-002
No limit
Total suspended solidsAt RSW-001 and RSW-002
No limit
TurbidityAt RSW-001 and RSW-002
No limit
Reported values over the permit's limit
Monthly reports the facility filed with the EPA, compared with the permit's limit for the same measure. A value counts only when it was detected and the limit was in force on that date.
Every value over the limit, by date (3)
Period ending
Parameter
Measure
Reported
Limit
Over by
Feb 28, 2026
Total coliformEFF-001EPA lists this as a violation.
7-day median
4.5 MPN/100mL
2.2 MPN/100mL
105% over
Jan 31, 2026
Total coliformEFF-001EPA lists this as a violation.
7-day median
11 MPN/100mL
2.2 MPN/100mL
400% over
Dec 31, 2025
Total coliformEFF-001EPA lists this as a violation.
7-day median
4.5 MPN/100mL
2.2 MPN/100mL
105% over
Violations the Water Board recorded
Not available. The Water Board's violation records for this kind of facility are not published as data we can read.
Enforcement actions
Notices, orders, and penalties the Water Board issued.
Date
Action
Details
Penalty
Apr 13, 2023
Administrative Civil LiabilityOrder R1-2023-0024
Graton CSD Settlement Agreement and Stipulation for Entry of Administrative Civil LiabilityStatus: Historical
Penalty required
Nov 9, 2022
Expedited Payment LetterOrder R1-2022-0041
The Water Board marks this as a mandatory minimum penalty.Status: Active
Apr 12, 2011
Administrative Civil LiabilityOrder R1-2011-0051
Status: Active
Penalty required
Aug 17, 2009
Staff Enforcement Letter
Final Report for SEP for ACL R1-2005-0004 was not submitted on time. It is 7 months late.Status: Historical
Dec 11, 2008
Cease and Desist OrderOrder R1-2008-0109
Status: Active
Jun 27, 2008
Expedited Payment LetterOrder R1-2008-0083
The Water Board marks this as a mandatory minimum penalty.Status: Historical
Oct 25, 2007
Administrative Civil LiabilityOrder R1-2007-0055
The Water Board marks this as a mandatory minimum penalty.Status: Historical
Penalty required
Sep 15, 2005
Notice of Violation
Jan 18, 2005
Administrative Civil LiabilityOrder R1-2005-0004
VIOLATIONS DURING THE PERIOD OF JANUARY 1, 2000 THROUGH MAY 5, 2004.Status: Historical
Penalty required
Sep 17, 2004
Staff Enforcement Letter
DISCHARGER REQUESTED THE OPPORTUNITY TO CHANGE THE TIMESCHEDUL BECAUSE THE FAICLITY IS BEING TRANSFERED FROM THE SONOMA COUNTY WATER AGENCY TO THE GRATON COMMUNITY SERVICES DISTRICT FOR OPERATION.Status: Historical
May 13, 2004
Notice of Violation
Jul 12, 2000
Oral Communication
ALL EFFLUENT VIOLAITONS THAT OCCURRED AT THE GRATON PLANT BETWEEN JANUARY & JUNE 2000 WERE DISCUSSED WITH DEBBIE WEBSTER & HODY WILSON FROM THE SCWA IN A JULY 12, 2000 MEETING.Status: Historical
Aug 24, 1995
Cease and Desist OrderOrder 95-05702
NEW NPDES PERMIT WITH NEW TREATMENT.Status: Historical
Aug 24, 1995
Cease and Desist OrderOrder 95-05601
NEW NPDES PERMIT WITH NEW REGULATIONS OF TREATMENT.Status: Historical
Aug 25, 1994
Cease and Desist OrderOrder 94-106
CDO ISSUED WITH TIME EXTENSION ON COMPLIANCE DATES INCLUDED IN CDO 93-038.Status: Historical
Apr 1, 1993
Cease and Desist OrderOrder 93-038
DISCH THREATENING TO DISCH WW THAT IS NOT ADVANCED TREATED TO RUSSIAN RIVER IN VIOLATION OF WDRS.Status: Historical
Sewer spills from Graton CSD Graton CSA No. 2 CS
The same agency runs the sewer system that feeds this plant. Spills are reported under the State Water Board's sewer system order, a state program separate from this permit. Category 1 spills reached surface water.
About 2,015 people live in the neighborhood around this site in Sebastopol. The state scores it above 37% of California neighborhoods for pollution burden and health vulnerability.
Least burdenedMost burdened
Source: CalEnviroScreen 5.0, census tract 6097153712. The score covers the whole neighborhood and does not measure this site's own effect.